Singapore legislation
Regulation 10
Regulation 10
Storage of petroleum in quantities exceeding 12½ cases but not exceeding 100 cases
Before the Director grants a licence for the storage of petroleum in quantities exceeding 12½ cases but not exceeding 100 cases, the applicant shall provide within his premises in such a position as shall be approved by him one or more receptacles or storage bins for storing petroleum constructed of brickwork of a thickness of not less than 35 centimetres, and having a floor of cement concrete not less than 15 centimetres in thickness sloping to a small catch-pit; the cubic content of a bin shall measure and not exceed one-third more than the cubic content of the number of cases that are to be stored and the applicant shall carry out such structural alterations or additions to his own or adjacent premises as may be considered necessary by the Director.