Singapore legislation
Schedule 1
of Environmental Protection and Management (Regulated Goods and Registered Suppliers) Regulations 2022
Schedule 1
Requirements for regulated goods
FIRST SCHEDULERegulations 2 and 6Requirements for regulated goodsDefinitions
1. In this Schedule, unless the context otherwise requires —“AHRI” means the Air-Conditioning, Heating and Refrigeration Institute;“ISO” means the International Organization for Standardization;“single‑phase non‑ducted room air‑conditioner”, “single-phase variable refrigerant flow (VRF) air‑conditioner”, “split type (inverter) air‑conditioner” and “split type (non‑inverter) air‑conditioner” have the meanings given by Part 2 of the First Schedule to the Environmental Protection and Management (Prescribed Regulated Goods) Order 2022;“water-cooled chiller” has the meaning given by Part 2 of the Second Schedule to the Environmental Protection and Management (Prescribed Regulated Goods) Order 2022.Global warming potential limits
2. The global warming potential limits set out in the second column applies to the regulated goods specified opposite in the first column:First columnSecond column1.Electrically driven water‑cooled chillers with a cooling capacity of 1,055 kW or more152.Single-phase non-ducted room air‑conditioner (split type (inverter)) with cooling capacity of 17.6 kW or lower, that is not a single‑phase variable refrigerant flow (VRF) air‑conditioner7503.Single-phase non-ducted room air‑conditioner (split type (non‑inverter)) with cooling capacity of 17.6 kW or lower 7504.Single-phase refrigerator with an adjusted volume of up to 900 litres15Test standard or method
3. The prevailing test standard or method applicable to regulated goods in the first column that are of a type in the second column, is specified in the third column opposite that type of goods:First columnSecond column Third columnRegulated goodsType Prevailing test standard or method(a)Air-conditioner(i)Split type (inverter) with more than one indoor unit—ISO 15042 (2017)At least one cooling test must be conducted at the full‑load cooling capacity(ii)Split type (inverter) with one indoor unit—ISO 5151 (2017)At least one cooling test must be conducted at the full‑load cooling capacity(iii)Split type (non-inverter) with more than one indoor unit—ISO 15042 (2017)(iv)Split type (non-inverter) with one indoor unit—ISO 5151 (2017)(b)ChillerAll —AHRI 551/591‑SI-2018At least one cooling test must be conducted at the full‑load cooling capacity(c)RefrigeratorAll—ISO 15502 (2005) or IEC 62552 (2007)