Requirements for water fittings
Subregulation 1
Every water fitting shall be —
of an appropriate quality and standard;
suitable for the circumstances in which it is used;
if used for the conveyance of piped water suitable for drinking supplied by the Board, fit for such conveyance;
except in the case of exposed terminal fittings such as taps, resistant to dezincification if such fitting is made of brass; and
capable of withstanding a hydrostatic field test pressure of not less than 12 bars or an internal water pressure of not less than 1½ times the maximum pressure to which the fitting is designed to be subjected in operation, whichever is the greater.
Subregulation 2
For the purposes of paragraph (1)(a), a water fitting is of an appropriate quality and standard only if it conforms to every requirement applicable to it specified in the PUB S&R Standard.
Subregulation 3
For the purposes of paragraph (2), a water fitting shall be treated as conforming to the applicable requirements mentioned in that paragraph if the water fitting is certified or tested as conforming to those applicable requirements by —
an accredited laboratory; or
such other testing laboratory as the Board may allow.
Subregulation 4
[Deleted by S 341/2020 wef 30/04/2020]